Why can't the voltage transformer be short-circuited and the current transformer can't be opened?

Apr 19, 2021

Leave a message

We all know that voltage transformers cannot be short-circuited and current transformers cannot be operated in an open circuit. Once the voltage transformer is short-circuited or the current transformer is open-circuited, it will damage the transformer or cause danger.


In principle, we all know that both voltage transformers and current transformers are transformers, but the parameters of concern are different. So why the same transformer cannot run in a short circuit and run in an open circuit?

image

Transformer schematic


In normal operation, the secondary coil of the voltage transformer is equivalent to an open circuit, and the impedance ZL is very large. If the secondary circuit is short-circuited, the impedance ZL will rapidly decrease to almost zero. At this time, the secondary circuit will generate a large short-circuit current, which will Damage to secondary equipment or even endanger personal safety. The voltage transformer can be equipped with a fuse on the secondary side to protect itself from being damaged by a short circuit on the secondary side. Where possible, a fuse should also be installed on the primary side to protect the high-voltage power grid from endangering the safety of the primary system due to transformer high-voltage winding or lead failure.


When the current transformer is in normal operation, the impedance ZL is very small, which is equivalent to the operation of the secondary coil in a short-circuit state. The magnetomotive force generated by the secondary current demagnetizes the magnetic potential generated by the primary current. The excitation current is very small, the total magnetic flux in the iron core is very small, and the induced electromotive force of the secondary winding does not exceed tens of volts. If the secondary side is open, the secondary current is equal to zero, and the demagnetization effect disappears, but the ε1 of the primary coil remains unchanged, and its primary current completely becomes the excitation current, causing the magnetic flux Φ in the iron core to increase sharply, and the iron core is in a highly saturated state. In addition, the number of turns of the secondary winding is large, and a very high voltage (even thousands of volts) will be generated at both ends of the secondary winding, which may not only damage the insulation of the secondary winding, but also seriously endanger personal safety. Therefore, an open circuit on the secondary side of the current transformer is absolutely not allowed.

Voltage transformers and current transformers are both transformers in principle. Voltage transformers pay attention to changes in voltage, and current transformers pay attention to changes in current. So why the same is the transformer, the current transformer cannot operate in an open circuit, and the voltage transformer cannot operate in a short circuit?


In normal operation, ε1 and ε2 remain unchanged. The primary side of the voltage transformer is connected in parallel in the loop, the voltage is relatively high, the current is very small, and the current on the secondary side is also very small and almost zero during normal operation, forming a relative balance with the open circuit infinite impedance in the secondary loop. When the secondary side impedance quickly decreases to a short circuit, because ε2 remains unchanged, the secondary current will inevitably increase rapidly and burn out the secondary coil.


The same principle, in normal operation, ε1 and ε2 remain unchanged. The primary side of the current transformer is connected in series in the loop. The current is relatively high and the voltage is very small. During normal operation, the voltage on the secondary side is also very small and almost zero, forming a balance with the infinite short-circuit impedance in the secondary loop. When the impedance of the secondary circuit increases rapidly to an open circuit, the secondary current quickly drops to zero, and all the primary current is converted into the excitation current, causing the magnetic flux to rapidly increase to saturation and burn out the transformer.


So the same transformer, the application is different, the result will be different.