What are the losses of the transformer?
Apr 23, 2021
Leave a message
The magnetic flux of the transformer primary coil and secondary coil are the same. But in fact, the transmission of the magnetic field is accompanied by loss, which can be roughly divided into the following situations:
1.Eddy current loss
2.Hysteresis loss
3.Magnetic leakage loss
一. Eddy Current Losses
Faraday said that a changing magnetic field can generate electricity, and Lenz said that this kind of electricity will hinder the change of the magnetic field, which is called Back EMF.
The magnetic core of the transformer is in a changing magnetic field, and electricity will also be generated on it, showing a lot of small eddy currents. This phenomenon is called the eddy current effect (Eddy Current).

Figure 1-Eddy Current phenomenon (Eddy Current)
Eddy current is useful in some situations, for example, home appliance induction cookers are based on the principle of eddy current to heat food. But it will cause loss in the transformer.
In order to solve the eddy current problem, there are two ideas:
Decompose the large magnetic core into a large number of small magnetic cores, such as laminated, powder, etc.;
Use high resistivity materials, such as ferrite ceramics, silicon steel and other materials;
1. Lamination
For the "口" type or "日" type cores in the transformer, they are not a single cylinder, but are composed of many layers of magnetic chips. There is insulation between the magnetic chip and the magnetic chip, which makes the eddy current can only be generated in a very narrow area (the area is perpendicular to the magnetic field). Since the size of the eddy current is proportional to the area, this can greatly reduce the eddy current. And, the thinner the magnetic chip, the better the effect.

Figure 2-Transformer core monomer (left) vs. laminated (right), where B represents the magnetic field and red represents the eddy current

Figure 3-The laminated core of the transformer ("日"/"E+I" font)
2. Ferrite
Ferrite is a ceramic material with iron oxide as its main component. Most ferrites are magnetic materials used to make permanent magnets (hard ferrites) and transformers (soft ferrites) cores. The high resistivity of ferrite itself can reduce the phenomenon of eddy current.
二. Hysteresis Losses
The so-called hysteresis means that the magnetization of a substance not only depends on the external magnetic field "at that time", but also on the result of "before" magnetization. That is, once it is magnetized, the magnetism will remain. To demagnetize, it is necessary to apply a magnetic field in the opposite direction.
We can see the clues from the B-H curve:
The symbol B refers to the magnetic flux density (Magnetic Flux Density), which is also translated as magnetic induction intensity in China. I think the former is more accurate;
The symbol H refers to the magnetic field strength (Magnetizing Force), which is the magnetomotive force per unit length (described above), which can be understood as being proportional to the current passing through the coil;

Figure 5-B-H curve
The evolution process is:
The origin (a) of the coordinate axis indicates that the material is not magnetized, and then a positive current is input to the coil (the H axis is positive), the material shows magnetism, and the magnetic flux is positive (red dotted line);
When the current increases to a certain extent, the magnetic flux increases slowly and enters the magnetic saturation state (b);
If the current stops, the substance can still show magnetism (c);
The magnetism will disappear only by applying a reverse current (d).
In the transformer, the magnetic core is repeatedly magnetized by alternating current. We hope that the magnetic hysteresis of the magnetic core is as small as possible, otherwise more energy will be wasted in overcoming the hysteresis.
三. Leakage Magnetic Flux
Although the magnetic core has a high magnetic permeability, there is always some magnetic flux that does not propagate along the magnetic core, and they leak to the outside, which is called magnetic leakage.

Figure 7-Leakage Flux
Magnetic leakage does not participate in the magnetic coupling energy transfer between the primary coil and the secondary coil. They are like inductors, connected in series in a circuit. Inductance acts as an impedance and will produce a voltage drop, so the actual voltage on the transformer will be smaller:

Figure 8-Transformer equivalent circuit (simplified series of inductors)
In summary, we explained the loss phenomenon on the transformer. When the secondary coil is open, a small current will pass through the primary coil. Part of this current is the magnetizing current (Magnetizing Current), and the other part is the current caused by the loss (Core Loss Current). The sum of the two is called the excitation current (Exciting Current).
For more information, please contact us at sales@xfullstar.com