How to Choose the Right CT Size?

Apr 17, 2026

Leave a message

A Current Transformer (CT) is a type of instrument transformer designed to produce an alternating current in its secondary winding which is proportional to the current being measured in its primary. Selecting the correct "size"-which encompasses the ratio, accuracy class, burden, and physical dimensions-is the cornerstone of power system reliability.

This guide breaks down the selection process into technical pillars to ensure your system operates with precision and safety.

1. Understanding the Transformation Ratio

The first step in choosing a CT size is determining the Current Ratio. This is expressed as the ratio of the primary current to the secondary current (e.g., 100:5A or 1000:1A).

Primary Current Selection

The primary current rating ($I_p$) should be based on the maximum continuous load current of the circuit.

  • Rule of Thumb: Select a primary rating that is approximately 10% to 20% higher than the maximum expected current.
  • Common Standard: If your maximum load is 320A, a 400A primary CT is typically the standard choice. Choosing a primary that is too high results in low sensitivity at smaller loads; choosing one too low leads to saturation.

Secondary Current Selection

Standard secondary ratings are usually 5A or 1A.

  • 5A Secondary: The industry standard for short distances between the CT and the meter/relay (typically under 10 meters).
  • 1A Secondary: Preferred for long-distance transmissions. Because power loss in cables is calculated as $P = I^2R$, a 1A secondary reduces lead loss by a factor of 25 compared to a 5A secondary, making it much more efficient for remote monitoring. 

2. Accuracy Class and Application

CTs are generally divided into two categories: Metering and Protection. You cannot use a "size" designed for one in the application of the other.

Metering CTs

These require high accuracy at normal operating currents but must saturate at high currents to protect the connected meters from damage during a fault.

  • Common Classes: 0.2s, 0.2, 0.5s, 0.5.
  • The "S" Factor: Classes like 0.2s are "special" accuracy classes that maintain high precision even at very low loads (as low as 1% of the rated current), which is vital for revenue billing.

Protection CTs

These must remain linear (not saturate) during massive overcurrent or short-circuit events to ensure the protective relays can trip the circuit breaker.

  • Common Classes: 5P10, 10P20.
  • Interpretation: In "5P10," the "5" is the percentage error, and "10" is the Accuracy Limit Factor (ALF). This means the CT will have no more than 5% error at 10 times the rated primary current.

3. Calculating the Rated Burden

The "size" of a CT isn't just about current; it's about power capacity, known as Burden. Measured in Volt-Amperes (VA), burden is the total resistance (impedance) the CT secondary must drive.

To choose the correct VA rating, you must sum the following:

  1. Device Burden: The power consumption of the connected meters or relays (check the manufacturer's datasheet).
  2. Lead Wire Burden: The resistance of the copper wires connecting the CT to the device.
  3. Contact Resistance: Typically a small safety margin (approx. 0.1 to 0.5 VA).

Calculation Tip:

$$VA = I^2 \times R_{total}$$

If the total calculated burden is 8VA, you should select a CT with a standard rating of 10VA. If you choose a CT with a VA rating that is too low, the accuracy will drop. If it is significantly too high, the CT may not saturate when it should (in metering cases), potentially damaging equipment.

 

4. Physical Dimensions and Installation Type

In the world of CTs, "size" also refers to the physical footprint. You must match the CT to your installation environment.

Split-Core vs. Solid-Core

  • Solid-Core CTs: Best for new installations where cables or busbars can be threaded through the window during construction. They offer the highest accuracy and longevity.
  • Split-Core CTs: Essential for retrofitting. The core "snaps" open, allowing installation without disconnecting the primary conductor. This saves significant labor costs and prevents downtime.

Window Size (Inner Diameter)

Ensure the "window" or hole of the CT is large enough to accommodate your cables or busbars.

  • For Cables: Account for the insulation thickness, not just the copper core.
  • For Busbars: Measure the width and number of bars in the stack. It is recommended to have at least a 5-10mm clearance to avoid mechanical stress.

5. Insulation Level and Voltage Rating

The CT must be rated for the system voltage it is installed on.

  • Low Voltage (LV): Typically up to 600V or 1000V.
  • Medium/High Voltage (MV/HV): These require cast-resin insulation or oil-filled tanks to handle stresses of 11kV, 33kV, or higher.

Even if you are measuring a 100A current, if that current is flowing through a 10kV line, the CT must be sized for 10kV insulation.

6. Environmental and Safety Factors

Finally, consider where the CT will live.

  • Indoor vs. Outdoor: Outdoor CTs require UV-stabilized casings and higher IP (Ingress Protection) ratings (e.g., IP65 or IP67) to withstand rain and dust.
  • Temperature: High ambient temperatures can derate the CT's performance. Ensure the CT's thermal rating exceeds your environment's peak heat.
  • Safety (Open Circuit): Never "size" a CT without considering the safety of the secondary circuit. An open-circuited CT secondary can generate thousands of volts. If the application requires frequent disconnection, consider Voltage Output CTs (333mV) or CTs with built-in overvoltage protection.

Summary Checklist for Choosing a CT

To ensure you get the right product, always provide the following five parameters to your manufacturer:

Parameter

Example Requirement

Ratio

500:5A

Accuracy Class

0.5 for Metering / 5P10 for Protection

Rated Burden

10VA or 15VA

Inside Diameter

50mm (Circular) or 60x20mm (Busbar)

System Voltage

0.66kV (Low Voltage)

Conclusion

Choosing the right CT size is a balance of electrical precision, physical constraints, and safety requirements. By selecting the appropriate ratio, ensuring the accuracy class matches the application, and accurately calculating the VA burden, you protect your infrastructure and ensure the integrity of your data.