High-voltage Power Transformer

Jun 23, 2016

Leave a message

Basic Info

  • Model NO.: FPT 230/35KV

  • Phase: Three-phase

  • Cooling Method: Oil-immersed Type Transformer

  • Test Certification: Kema Transformer Test

  • Specification: IEC Standard

  • HS Code: 8504231200

  • Application: Power system, Electronic, Instrument, Rectifier

  • Coil: Core-type Transformer

  • Winding Type: Two-winding / Three windingTransformer

  • Trademark: FULLSTAR

  • Origin: China

Product DescriptionPower Transformer
230-242kV on-load-tap-changing power transformer is made of high-quality silicon-steel sheets, and laminated by steps. It is advantageous in low loss, low noise, low voltage partial discharge and high anti short-circuit capacity. The dynamical and thermal stability of this transformer, of which the coils are winded by high-quality oxygen-free copper wire as well as used pre-compressing brackets processes and interior and exterior structure. The transformer tank used wave form shell, has very nice appearance, the core is with D shape yoke and 45 angle seaming. The core and oil box are well fixed and well protected on moving.
Three-phase dual winding oil immersed power transformer with OLTC
Type: FPT-230
Rated voltage: 230/34 kV
Rated capacity: 100000/120000kVA
Rated voltage ratio: 230± 8× 1.25%/34kV
Rated current: 301/2038A
Phase number: Three
Rated frequency: 50 Hz
Connection: Ynyn0(d11)
Voltage regulating method: Neutral point on-load Regulating
Short circuit impedance: 9.5%(10MVA)
Cooling mode: ONAN/ONAF
Contact info :  sales@xfullstar.com   Phone : 86-29-86676405 


Lightning impulse withstand voltage(kV peak value)1minMain frequency withstand voltage
(kV RMS)

Full waveChopped wave

High voltage side10501175460
Neutral point of high voltage(1050)
(460)
Low voltage side17018570
Neutral point of low voltage170
70

14 th. Insulation Level: A                                                            

15 th. Field strength between transformer winding turns is no more than 2kV/mm        

16 th. Transformer loss (under 75) no-load current and efficiency                     

No-load Loss: 92 kW              According to IEC standard                            

Load Loss: 356 kW                According to IEC standard                            

No-load current: 0.3 %          According to IEC standard                            

17 TH. Radio interference and corona

Under the Maximum phrase voltage, corona is not visible from outgoing terminal in the night of clear day at outdoor. Radio interference voltage is no more than 2500Uv 

18 th. Overloading capability        

Short-time overloading capability of transformer and overload running time are as follow 

Over current30456075100
Allowable running time min12080452010